Operations
• Measurement Range: Alarm or Normal
• Sensor Type: Infrared sensor dual element
• Detection Angle: 60°
• Maximum working distance: 9 feet
Power/Environmental
• Source: Powered by the environmental monitoring appliance unit - no additional power needed
• Power Consumption: Typical 50 mWatt, 10mA
• Operating Temperature: 4°~122°F; -20°~50°C
Physical
• Dimensions (W x H x D): 2.55 x 2.44 x 0.59 in. (65 x 62 x 15 mm)
• Mounting: Wall/ceiling mounted design; DIN rail mounting; Screw mounting
• Communications Cable: UTP CAT-5e/6 cable with 2x RJ45 connectors (to connect sensor to sensorProbe or securityProbe monitoring appliance)
• Maximum Cable Length (Single Motion Detector): 1000 feet, using standard UTP CAT-5e/6 cable
• Maximum Cable Length (string of 10 Motion Detectors): 150 feet, using standard UTP CAT-5e/6 cable, with 20 feet maximum cable length between each motion detector