Copyright © 2024 KVMGalore® - All rights reserved.
Operations
• Measurement Range: Wet or Dry
• Sensor Type: Open/Closed contact input switch
• Measurement Rate: Multiple readings every second
• Able to detect the presence or non-presence of water
• Full autosense including disconnect alarm
• Indication: LED for Status
• Pull Force Limit: Not to exceed 50 lb
• Bend Radius: 2 in. (50 mm) minimum
• Pressure: Loads greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger an alarm
Interface
• Communications Cable: UTP CAT-5 cable from RJ-45 jack to sensor port on AKCP environmental monitoring appliance unit
• Max. Interface Cable Length: 200 feet, standard UTP CAT-5/6 cable
Environment
• Operating Temperature: 4°~140°F; -20°~60°C
Power
• Source: Powered by the environmental monitoring appliance unit - no additional power needed
• Consumption Typical 125 mWatt, 25 mA
Physical
• Sensing Cable Length: 10 feet; Extendable up to 100 feet
• Non-Sensing Cable Length: 20 feet
• Dimensions: 2.2 x 2.16 x 1.3 in. (56 x 55 x 33 mm)
• Mounting: DIN rail mounting; Screw mounting