Copyright © 2024 KVMGalore® - All rights reserved.
Operations
• Temperature Measurement Range: -67° to +167°F (-55° to +75°C)
• Humidity Measurement Range: 0 to 100% Relative humidity
• Humidity Resolution: 1%RH increments, 0.01%RH sensor reading
• Sensor Type: Semiconductor, microprocessor controlled
Calibiration
• NIST traceable Calibration Certificate
• Built in calibration check
• Alerts when sensor needs re-calibration
Interface
• Communications Cable: RJ-45 jack to sensor using UTP CAT-5 cable
• Communications Cable Max. Length: 330 feet standard CAT-5/6 UTP cable
Temperature Measurement Resolution sensorProbe+ Series
• 0.1°C increments
• 0.2°F increments
Temperature Measurement Resolution securityProbe Series
• 0.5ºC increments
• 0.9ºF increments
Temperature Measurement Accuracy
• ±0.5°C accuracy from -10° to +75°C
• ±0.9°F accuracy from +14° to +167°F
Humidity Accuracy at 25°C
• Min: ±2%RH
• Max: ±5% RH
Power
• Source: Powered by AKCP environmental monitoring appliance - no additional power needed
• Consumption: Typical 17.25mWatt, 1.45mA
Physical
• Mounting: DIN rail mounting and screw mounting
• Dimensions: 2.16 x 2.16 x 1.06 in. (55 x 55 x 27 mm)