Electrical
• Nominal Input Voltage: 100 – 120 VAC
• Maximum Input Current: 20A (Max), 16A (UL de-rated)
• Input Frequency: 50-60 Hz
• Input Connection: NEMA 5-20P
• Input Power: 2400VA (Max)
• Outlet Type: 14x NEMA 5-15R + 2x NEMA 5-20R
• Outlet Banks: 2 (each bank consists of 7x NEMA 5-15R + 1x NEMA 5-20R outlets)
• Nominal Output Voltage 100-120 VAC
• Maximum Output Current (Outlet): NEMA 5-15R - 15A;(Max); NEMA 5-20R - 20A (Max)
• Maximum Output Current (Bank): 20A (Max)
• Maximum Output Current (Total): 20A (Max)
• Breaker: 1x 20A non-fuse breaker
• Metering (per bank level): Current, Voltage, VA, PF, and KWh monitoring
• Outlet Switching: Yes
• Environment Sensor Ports: 2
Metering Accuracy
• Voltage range: 100VAC ~ 250VAC +/-1%
• Power range: 100W ~ 5000W +/- 2%
• Current range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Environmental
• Temperature (Operating/Storage): 0 – 50℃ / -20 – 60℃
• Humidity (Operating and Storage): 0–80% RH, Non-Condensing
Physical
• Dimensions (L x W x H): 132.48 x 6.6 x 4.4 cm (52.16 x 2.6 x 1.73 in.)
• Weight: 3.73 kg (8.22 lb)
• Power Cord Length: 3 m
Compliance
• EMC Verification: FCC
• Safety Verification: cTUVus, PSE