Copyright © 2024 KVMGalore® - All rights reserved.
Input
• Voltage: 400V
• Plug: 230/400V Wye 32A IEC 60309 3P+N+PE 6Hr
• Current: 32A
• Current Rated: 32A
• Power Capacity: 22.0 kW
• Branch Circuit Protection: UL489 Compliant 1-pole, 20A trip circuit breakers, six (6) branch, rating: ≤ 16A, 10 kAIC Interrupt Rating
Outputs
24x IEC 60320/C13 North American Rating: ≤ 12A @208V L-L (15A Peak)
6x IEC 60320/C19 North American Rating: ≤ 16A @208V L-L (20A Peak)
Input Measurement Accuracy
• LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
• GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
• Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
• Active Power = ± 1% at 1 watt resolution
• Apparent Power = ± 1% at 1 volt-amp resolution
• Power Factor = ± 3% at 0.01 resolution
• Crest Factor = ± 10% at 0.1 resolution
• Energy = ± 1% at 0.1 kilowatt-hour resolution
Communications and Security
• 10/100/1000 Mbps Ethernet (RJ-45 connector)
• RS-232 serial (RJ-45 connector)
• Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU}
• Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Environmental
• Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
• Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
• Quiescent / Unloaded Power Draw: < 10W for all configurations
Certifications
• TUV T-Mark to EN 60950-1:2006+A11+A1+A12+A2
• EMC to EN55024 (2010) and EN55032 (2012)
• CE Compliant
• RoHS, European Hazardous Materials Directive (Recast) 2011/65/EU
• WEEE Compliant
Physical
• Dimensions: 70.1in tall x 1.75in wide x 2.25in deep [1781mm x 45mm x 58mm]
• Input Cord Location: Bottom/Pivot
• Cord length: 10 feet