Copyright © 2024 KVMGalore® - All rights reserved.
• Quantity of inputs: 1
• Voltage: 200-240V Delta
• Current: 60A x 3 Phase DELTA
• VA per input (load capacity): 17.2kW
• Frequency: 50/60 Hz
• Over current protection: (6) 20A Double Pole Magnetic Breakers
• On/off switch: Breaker/Switch Combination
• Scrolling/rotatable digital display: Yes
• Power cable wire gauge: 4/4
• Power cable length: 10 feet
• Power entry location: Bottom front
• Plug type: IEC60309 3P + E, 60A, Splashproof IP44
• Internal RMS voltage sensor: Yes
• Internal RMS current sensor: Yes
• Network connection: Dual 10/100Mbps Ethernet
• Network protocols supported: DHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog, TACACS+
• Data access formats: CSV datalog, JSON API, JSON datalog
• USB support: Yes
• IP reset button: Yes
• Hard reboot button: Yes
• Serial connection: RS232 via RJ45
• Remote sensor RJ connection jacks: 1 (supports up to 16 sensors)
• Maximum operating temperature: 60C° / 140F°
• Heavy steel - powder coat finish: Black
• Configuration: 72 in. / 1829 mm vertical
• 7938 vertical mounting bracket kit: Yes
• Toolless mounting hardware - Center to center spacing 61.25 in. and 64.75 in.
• Made in the USA: Yes
• Warranty: 5-year limited warranty if registered within 120 days of purchase, otherwise warranty defaults to 3 years
• Certification/agency approvals: RoHS compliant; UL & c-UL Listed 60950; FCC Part 15 Class A conformance
• Chassis dimensions (LxWxD): 72 x 2.25 x 3.44 in.
Receptacle/Socket
• Combined total receptacle/socket quantity: 24
• Type: IEC C13
• Quantity on face: 12
• Quantity per breaker: 2
• Quantity per phase combination: 4
• Style: Banks of 2
• Voltage per receptacle/socket: 208V
• Type: IEC C19
• Quantity on face: 2
• Quantity per breaker: 2
• Quantity per phase combination: 4
• Style: Individual
• Voltage per receptacle/socket: 208V